how to calculate kw required by underfloor pipe heating?

1. The supply water temperature and return water temperature of underfloor heating system should be determined by calculation, the supply water temperature should not exceed 60°C, civil buildings supply water temperature should be around 35℃ to 50℃, temperature difference should not exceed 10℃.

underfloor heating system linsam

2. Average temperature of ground surface (℃)

AreaSuitable range(℃)Highest limit(℃)
People always stay area24-2628
People temporary stay area28-3032
People not stay area35-4042

3. Thickness of insulation layer of polystyrene foam.

Floor typeInsulation material thickness(mm)
Insulation layer on floor between floors20
Thermal insulation on the floor adjacent to the soil or unheated rooms30
Thermal insulation on the floor adjacent to outdoor air40

4. When calculating the heat load of a comprehensive ground underfloor heating system, the calculated indoor temperature should be 2°C lower than the calculated indoor temperature of the convective heating system, or 90% to 99% of the total heat load calculated by the convective heating system.

5. The heat load of the local floor underfloor heating system can be determined by multiplying the heat load calculated from the overall radiant heating of the entire room by the ratio of the area of the area to the area of the room and the additional coefficients specified in the following table.

Ratio of heating area to total room area0.550.40.25
Additional factor1.31.351.5

6. For rooms with a depth greater than 6m, it is advisable to take 6m away from the outer wall as the boundary zone to calculate the heat load and arrange the pipelines separately.

7. On the building ground where heating pipes are laid, the heat transfer loss of the ground should not be calculated.

8. The heat load calculation of the ground underfloor heating system does not need to consider the height addition.

9. The heat load calculation of the floor underfloor heating system with household heat metering should consider factors such as intermittent heating and heat transfer between households.

Check the table method to determine the floor heating pipe spacing:

The heat dissipation Qr and the downward heat transfer loss Qs per unit ground area of the PE-X tube (W/㎡)

The outer diameter of the tube is 20mm, the thickness of the filling layer is 50mm, the thickness of the polystyrene foam insulation layer is 20mm, and the temperature difference between the supply and return water is 10℃ (cement or ceramic floor, thermal resistance R=0.02(㎡.k/w))

Average water tempIndoor tempHeating pipe spacing (mm)
300250200150100
QrQsQrQsQrQsQrQsQrQs
351684.723.892.524100。524.6108.924.8116.624.8
1876.421.783.32290.422.697.922.7104.722.7
206819.97420.280.420.587.120.593.120.5
401610829.7118.129.8128.730.5139.630.8149.730.8
1899.527.4108.727.9118.428.5128.428.7137.628.7
209125.499.425.7108.126.5117.326.7125.626.7
4516131.835.5144.435.5157.536.5171.236.8183.936.8
18123.333.2134.833.91734.5159.834.8171.634.8
20144.531.7125.332136.632.4148.532.7159.332.7

The heat dissipation Qr and the downward heat transfer loss Qs per unit ground area of the PE-X tube (W/㎡).

The outer diameter of the tube is 20mm, the thickness of the filling layer is 50mm, the thickness of the polystyrene foam insulation layer is 20mm, and the temperature difference between the supply and return water is 10℃ (wood floor, thermal resistance R=0.1 (㎡.k/w))

Average water tempIndoor tempHeating pipe spacing (mm)
300250200150100
QrQsQrQsQrQsQrQsQrQs
351664.224.466.024.669.625.073.125.576.226.1
1856.322.359.622.562.822.965.923.368.723.9
2050.320.153.120.556.020.758.821.161.321.6
401679.130.283.720.788.431.292.831.996.932.5
1872.928.377.228.681.531.292.831.996.932.5
2066.826.370.726.574.626.978.327.481.728.1
451696.036.4101.836.9107.537.5112.938.2117.939.1
1889.834.195.134.8100.535.3105.636.0110.236.8
2083.632.288.632.793.533.198.233.8102.634.5

Estimated heating  design:

Building typeAdvised underfloor heating kw data 
No insulation measuresInsulation measures have been taken
Residential58-6440-45
Comprehensive residential area60-6845-55
School, office60-6850-70
Hospitals, kindergartens65-8055-70
Hotel60-7050-60
Shop65-8055-70
Canteen115-140100-130
Theaters, exhibition halls95-11580-105
Auditorium115-165100-150

Remarks:

1. In the plan design stage, in the absence of basic data, the heating load can be estimated based on the thermal index. When conditions permit, the load calculation should be carried out room by room and item by item.

2. The thermal index is used in a single room, and the error may be large.

3. The table is based on continuous heating, intermittent heating index = continuous heating index × 24/day heating hours.

Leave a Comment

Your email address will not be published. Required fields are marked *

Scroll to Top