Product Catagory
Cooling heat pump system (9KW to 23KW)
The cooling heat pump system TAN-R series usually applicable for normal temp or lower at -15°C, it can provide heating in winter and cooling in summer, connect to indoor terminal as fan coils, convectors or air conditioning fan unit.
It has Below add-on options:
1. Produce stainless steel casing
2. Add electric bottom heater
3. Add soft starter
4. Wifi controller
Get a quick quote
Product Features
- High-efficient scroll compressor Copeland / Sanyo / Daikin.
- R410A or R407C or R417A refrigerant.
- Base frame external panels made of polyester powder coated steel or stainless steel.
- Reverse cycle valve.
- Compact structure and sound control design.
- Water side equipped with efficient tank type heat exchanger.
- Automatic anti-freeze and defrosting function.
- Careful protection functions as high pressure. low pressure, overheating, overload, anti-freezing, phase order, discharge temp, etc.
- General testing and operational test carried out for every unit before package in the factory
Comparison of different heating method
Compared electric heater, the heat pump cost only 25% can produce 1 unit heating, while electric heater need 100% power consumption.
Main Components
Compressor
Our products adopts America Copeland scroll compressor for bigger heat pump and Panasonic compressor for smaller ones,, special designed for heat pump, working high efficiency.
Electronic expansion valve
With branded Sanhua expansion valve and combine with our company’s control system, we have developed a special electronic expansion controller that uses digital technology to adjust the refrigerant according to temperature factors to achieve the best flow rate effect and achieve higher COP.
Electrical control system
With project control function, it can easily control the circulating pump, water compensation, water supply, auxiliary electric heating, PID automatic defrost. Users can set different parameters according to different project needs, and automate the entire system.
Shell and tube heat exchanger
Linsam heat pump adopts high-efficiency shell and tube heat exchanger, the heat exchange area is 3.7 times that of bare tube, its unique design and compact spiral structure of the heat
exchanger ensures the full heat exchange of the refrigerant.
Heating cooling heat pump system options
We provide OEM and ODM services
Stainless steel casing
The heat pump cover produce with stainless steel casing can protect from rust, special by seaside installation.
Addon bottom heater
With eelctrical bottom heater tap by bottom of the air source heat pump, it avoid freezing of heat pump.
ABB soft starter
We can install ABB soft starter for your heat pump, the unit start more smoothly from 0 to rated voltage.
Add on wifi controller
With wifi controller you can set the heat pump by telephone, with the code it more conventional for our life.
Technical Parameters
Model | TAN-03R | TAN-05R | TAN-06R | TAN-07R |
---|---|---|---|---|
Heating capacity kW | 9.2 | 16.3 | 19 | 22.5 |
Input power kW | 2.7 | 4.65 | 5.4 | 6.2 |
Cooling capacity kW | 7.6 | 13.5 | 16.2 | 18.5 |
Input power kW | 2.45 | 4.35 | 5.2 | 6 |
Input current A | 11.23/4.1 | 6.7 | 8 | 11 |
Max running current A | 17.1/7.5 | 12 | 14 | 16 |
Power source | 220V/380V | 380V/3N/50Hz | 380V/3N/50Hz | 380V/3N/50Hz |
Nosie level dB(A) | 55 | 62 | 62 | 63 |
Unit size mm | 710x710x840 | 750x750x1030 | 750x750x1030 | 920x860x1170 |
Unit quality kg | 115 | 145 | 155 | 175 |
Working temp range ℃ | '-15℃ - 43℃ | -15℃ - 43℃ | -15℃ - 43℃ | -15℃ - 43℃ |
Refrigerant | R410A/R417A/R407C | R410A/R417A/R407C | R410A/R417A/R407C | R410A/R417A/R407C |
Refrigerant charge qty kg | 1.7 | 2 | 2.3 | 2.5 |
Compressor qty pcs | 1 | 1 | 1 | 1 |
Water flow m3/h | 1.90 | 2.80 | 3.90 | 4.60 |
Conncetio in / out DN | 20 | 25 | 25 | 32 |
*Test condition 1. Cooling: ambient temp 35℃,AC side inlet water temp 1a2℃, outlet water temp is 7℃
2. Heating condition: Air source side DB/WB 7℃/6℃, AC side inlet water temp 40℃,outlet water temp 45℃
Related products
Cooling heat pump system (9KW to 23KW)
Air to water heat pump
Heat pump with AC function (32KW to 40KW)
Air to water heat pump
Industrial air chiller unit (48KW to 157KW)
Air to water heat pump
Installation places
The application of Linsam air source heat pumps include hotels, villas, private houses, apartments, supermarkets, flats, laundry, hair salons…
For Residential
Connect with underfloor heating pipes or convectors for house heating.
Heat pump install with water tank
For Commercial
Connect with fan coils /convectors for cooling and heating buildings.
Heat pump install without water tank
For Industrial
High temp hot water used for slaughter, printing, chemical places.